There are few words in commercial design that cause more confusion than “fire-rated.” A fabric can carry an impressive certification and still get rejected on inspection if it was tested to the wrong standard for the application.

The two standards most often mixed up are NFPA 701 and ASTM E84. Both deal with how textiles and materials respond to fire. Both are widely referenced in commercial specifications. But they measure different things, apply to different applications, and produce different kinds of results.

If you specify, manufacture, or procure commercial fabrics, knowing the difference between them isn’t optional. Getting it wrong costs time, money, and project momentum.

What NFPA 701 Actually Measures

NFPA 701 is the National Fire Protection Association’s standard test for flame propagation of textiles and films. It is specifically built for fabrics and films used in suspended or hanging applications.

Key characteristics:

  • Test type: Pass/fail
  • Method 1: Small-scale test for fabrics with an areal density of 21 oz/yd² or less, including single-layer fabrics, multilayer curtains and drapery, table skirts, table linens, display booth separators, and textile wall hangings
  • Method 2: Large-scale test for fabrics heavier than 21 oz/yd²
  • What it evaluates: Mass loss after burn, after-flame time, and burning drip behavior
  • Typical pass criteria: Mass loss not to exceed 40% average, after-flame not to exceed 2 seconds average, no burning drips that continue to flame on the floor

In short, NFPA 701 answers a single question: when this hanging textile is exposed to flame, does it propagate fire fast enough to make the situation worse?

What ASTM E84 Actually Measures

ASTM E84, sometimes called the Steiner Tunnel Test, measures surface burning characteristics of building materials. It is broader in scope than NFPA 701 and is applied to a wide range of construction and interior finish materials, including wall coverings.

Key characteristics:

  • Test type: Classification (Class A, B, or C), not pass/fail
  • Method: A 22-inch by 24-foot sample is mounted on the ceiling of a horizontal fire tunnel
  • What it evaluates: Flame Spread Index and Smoke Developed Index, compared against red oak and fiber-cement reference standards
  • Class A (most stringent): Flame Spread Index of 25 or less, Smoke Developed Index of 450 or less
  • Class B: Flame Spread Index of 26–75
  • Class C: Flame Spread Index of 76–200

ASTM E84 is the preferred test for textile wallcoverings, wall panels, and other permanent surface-mounted materials. Most public buildings require a Class A rating in interior finish applications.

When You Need NFPA 701

NFPA 701 is the right test when fabric is going to be hung, draped, or suspended. The International Fire Code (IFC) generally requires decorative materials—defined to include curtains, draperies, fabrics, streamers, and similar surface coverings—to meet NFPA 701.

Typical applications:

  • Stage curtains and theatrical drapes
  • Hotel and meeting room drapery
  • Hospitality cabana and outdoor enclosure fabrics
  • Trade show booth fabrics and table skirts
  • Healthcare cubicle curtains
  • Decorative banners and textile wall hangings (where not permanently affixed)

If your fabric is hanging in space and exposed on multiple sides, NFPA 701 is almost certainly the standard your local authority having jurisdiction (AHJ) will reference.

When You Need ASTM E84

ASTM E84 is the right test when textiles are being applied as a finished surface to walls or ceilings, especially when permanently installed.

Typical applications:

  • Textile wallcoverings in hospitality and corporate interiors
  • Acoustic wall panels wrapped in fabric
  • Permanently installed wall upholstery
  • Vinyl and synthetic wallcoverings in public buildings
  • Fabric-faced architectural panels

In most public-occupancy buildings, the interior finish must meet ASTM E84 Class A, defined by IBC Chapter 8 and NFPA 101 Life Safety Code. This is a stricter performance bar than NFPA 701 in practical terms—materials that pass ASTM E84 Class A will almost always pass NFPA 701, but the reverse is not true.

Common Specification Mistakes

A few patterns we see repeatedly:

  1. Specifying NFPA 701 for wall upholstery. This is the single most common error. If the textile is being permanently mounted to a wall, the inspector will ask for ASTM E84.
  2. Assuming “FR” is universal. A flame retardant treatment must be specifically tested and documented to the standard required for the application. “FR-treated” is not a specification.
  3. Confusing CAL TB 117 with NFPA 701 or ASTM E84. CAL TB 117-2013 covers cigarette ignition resistance for upholstered furniture. It is a different test for a different application.
  4. Not requesting test documentation up front. Test reports should travel with the fabric. Procurement teams should require them as part of the order, not chase them down after delivery.
  5. Treating “Class A” and “NFPA 701 Pass” as interchangeable. They aren’t. They measure different things on different equipment with different criteria.

Why Finishing Matters in Both

Many commercial fabrics start out beautiful but non-compliant. They achieve their fire performance only after being finished with the right flame retardant chemistry, applied to the right specification, and documented to the right standard.

A qualified finishing partner does three things:

  • Treats the fabric with FR chemistry appropriate for the application and substrate
  • Tests the finished material to confirm compliance with NFPA 701, ASTM E84, or both
  • Provides documentation that travels with the finished goods to support inspection and code review

Without all three, the fabric is unfinished business.

SBI Finishing: Your Partner in Fire Code Compliance

SBI Finishing offers Flame Retardant treatments and Fire Code Testing as core services, with the technical depth to match the standard your application requires—not just the one that’s easiest to certify against.

Our fire code services include:

  • Flame retardant finishing engineered to pass NFPA 701, ASTM E84, CAL TB 117-2013, and other relevant standards
  • In-house and partner testing support for compliance verification
  • Integration with stain protection, antimicrobial, and backing services for complete performance systems
  • Documentation that supports your project from spec through final inspection

Ready to Specify with Confidence

The right test for the right application is the difference between a project that passes inspection and one that gets sent back to procurement. Let’s get it right the first time.